Liquiphant FTL31
Endress+Hauser 5
Input
Measured variable
Density
Measuring range
> 0.7 g/cm³ (optionally available: > 0.5 g/cm³)
Output
Switch output
Switching behavior: On/Off
Function
3-wire DC-PNP:
Positive voltage signal at the switch output of the electronics (PNP), switching capacity 200 mA
2-wire AC/DC:
Load switching in the power supply line, switching capacity 250 mA
Operating modes
The device has two operating modes: maximum safety (MAX) and minimum safety (MIN).
By choosing the corresponding operating mode, the user ensures that the device also switches in a
safety-oriented manner even in an alarm condition, e.g. if the power supply line is disconnected.
Maximum safety (MAX)
The device keeps the electronic switch closed as long as the liquid level is below the fork. Sample
application: overfill prevention
Minimum safety (MIN)
The device keeps the electronic switch closed as long as the fork is immersed in liquid. Sample
application: Dry running protection for pumps
The electronic switch opens if the limit is reached, if a fault occurs or the power fails (quiescent
current principle).
Power supply
Supply voltage
DC-PNP:
AC/DC:
10 to 30 V DC, 3-wire
20 to 253 V AC/DC, 2-wire
Power consumption
DC-PNP:
AC/DC:
< 975 mW
< 850 mW
Current consumption
DC-PNP:
AC/DC:
< 15 mA
< 3.8 mA
Residual ripple
DC-PNP:
AC/DC:
5 Vss 0 to 400 Hz