Liquiphant FTL31
14 Endress+Hauser
Installation in vessels
If installed horizontally, pay attention to the position of the tuning fork to ensure that the liquid can
drip off easily.
The electrical connection, e.g. M12 connector, should be pointing down with the cable. This can
prevent moisture from penetrating.
G1/2
316L
A0021034
 4 Position of the fork in the case of horizontal installation in a vessel
Distance from wall
Ensure that there is sufficient distance between the expected buildup on the tank wall and the fork.
Recommended distance from wall ≥10 mm (0.39 in).
A0022272
Length of connecting cable
to1 000 m (3 281 ft)
max. 25 Ω/wire, total capacitance < 100 nF