Liquipoint T FTW 31, FTW 32
Endress + Hauser 17
Environment
Ambient temperature
range
Non-hazardous area
40 ... 70 °C
40 ... 60 °C (for FEW 58 NAMUR)
Storage temperature 40 ... 80 °C
Climate class Tropicalised as per DIN EEC 68, part 2-38
Degree of protection IP66
Shock resistance Practical test
Vibration resistance
(at min. rod length)
DIN 60068-2-64 / IEC 68-2-64: 20 ... 2000 Hz, 1 (m/s
2
)
2
/Hz
Electromagnetic
compatibility
Interference Emission to EN 61326, Electrical Equipment Class B
Interference Immunity to EN 61326, Annex A (Industrial)
Use for separte-instrumented probes a screened cable between the probe and the switching
unit.
For installation instructions for screened cables and general instructions for EMC inspection
conditions of E+H devices, see also TI 241F.
Process conditions
Medium temperature
limits
Permissible ambient temperature T
1
at the housing as a function of the measuring material
temperature T
2
in the vessel:
!
Note!
For separately instrumented devices (without FEW 5?) there are no restrictions in the indicated
temperature range.
Conductivity 10 µS
Limiting medium pressure
range
1 ... 10 bar
70
50
40
30
20
10
2030 10 10 30 40 50 60 7020 80 90
T
1
T
2
10
20
30
0
0
T
1
T
2
60
FEW 52, FEW 54
FEW 58 (NAMUR)
10040
40

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Liquipoint T Series and is the answer not in the manual?

Endress+Hauser Liquipoint T Series Specifications

General IconGeneral
BrandEndress+Hauser
ModelLiquipoint T Series
CategoryAccessories
LanguageEnglish

Related product manuals