Liquipoint T FTW 31, FTW 32
14 Endress + Hauser
Accuracy with built-in electronic insert
Reference operating
conditions
Ambient temperature: 23 °C
Medium temperature: 23 °C
Medium viscosity: medium must release the probe again (drain off).
Medium pressure p
e
: 0 bar
Probe installation: vertically from above
Measuring error +/ 10 % at 100 - 100 k
+/ 5 % at 1 k - 10 k
Repeatability +/ 5 % at 100 - 100 k
+/ 1 % at 1 k - 10 k
Hysteresis 10% for the MAX probe, in reference to the switch point. s φυνχτιον δεαχτιϖατεδ.
Switch-on delay < 3 s
Influence of ambient
temperature
< 0,05 %/K
Installation conditions
Installation instructions Mounting location
The rod and rope probes are mounted predominantly in tanks made of plastic or metal.
Piping (partially filled)
Two-rod probes can be used in piping as, for example, dry running protection for pumps.
L00-FTW3xxxx-11-05-xx-xx-001