5-point linearity protocol
The following points must be considered if option F4 (5-point linearity protocol) was selected in
feature 550 ("Calibration").
The 5 points of the linearity protocol are evenly distributed over the measuring range (0% - 100%).
Empty calibration (E) and Full calibration (F) must be specified in order to define the measuring
range
2)
.
The following restrictions must be considered when selecting E and F:
R R
A
A
F
F
E
E
A0019161
Version Minimum distance
between reference point R
and 100% mark
Minimum span Maximum value for
"Empty calibration"
FMR53/FMR54
Without antenna extension
A ≥ length of antenna +
200 mm (8 in)
1)
F ≥ 400 mm (16 in) E ≤ 20 m (66 ft)
FMR54 with antenna extension
2)
A ≥ length of antenna +
antenna extension +
200 mm (8 in)
3)
1) Minimum value for FMR53: 590 mm (23.6 in); minimum value for FMR54: 400 mm (16 in)
2) Feature 610 "Accessory mounted" option OM, ON, OR or OS
3) Minimum value: 400 mm (8 in)
The linearity check is performed under reference operating conditions.
The selected values for Empty calibration and Full calibration are only used to create the
linearity protocol. Afterwards, the values are reset to the default values specific for the
antenna. If values other than the default values are required, they must be ordered as a
customized parameterization.
2) If (E) and (F) are not specified, antenna-dependent default values will be used instead.