Operating menu Tankside Monitor NRF81
122 Endress+Hauser
Tank reference height
Navigation Setup → Tank reference height
Description Defines the distance from the dipping reference point to the zero position (tank bottom or
datum plate).
User entry 0 to 100 000 mm
Factory setting Dependent on the device version
Additional information
Read access Operator
Write access Maintenance
Tank level
Navigation Setup → Tank level
Description Shows the distance from the zero position (tank bottom or datum plate) to the product
surface.
Additional information
Read access Operator
Write access -
Level source
Navigation Setup → Level source
Description Defines the source of the level value.
Selection • No input value
• HART device 1 ... 15 level
• Level SR
*
• Level
*
• Displacer position
*
• AIO B1-3 value
• AIO C1-3 value
• AIP B4-8 value
• AIP C4-8 value
Factory setting Dependent on the device version
Additional information
Read access Operator
Write access Maintenance
* Visibility depends on order options or device settings