Tankside Monitor NRF81 Operating menu
Endress+Hauser 151
A0028602
48 The two relays of a digital output
1/2 The relays
3/4 The terminals of the digital output
The switching state of these relays is defined by the Output simulation parameter as
follows:
Output simulation State of relay 1 State of relay 2 Expected result on the
terminals of the I/O module
Simulating active Closed Closed Closed
Simulating inactive Open Open Open
Fault 1 Closed Open Open
Fault 2 Open Closed Open
The Fault 1 and Fault 2 options can be used to check the correct switching behavior
of the two relays.
Output value
Navigation Setup → Advanced setup → Input/output → Digital Xx-x → Output values
Prerequisite Operating mode (→ 148) = Output passive
Description Shows the digital output value.
Additional information
Read access Operator
Write access -
Readback value
Navigation Setup → Advanced setup → Input/output → Digital Xx-x → Readback value
Prerequisite Operating mode (→ 148) = Output passive
Description Shows the value read back from the output.