Tankside Monitor NRF81 Operating menu
Endress+Hauser 167
Assign TV
Navigation Setup → Advanced setup → Communication → HART output → Configuration
→ Assign TV
Description Assigns a tank variable to the third HART variable (TV).
Selection • None
• Tank level
• Tank ullage
• Measured level
• Distance
• Displacer position
• Water level
• Upper interface level
• Lower interface level
• Bottom level
• Tank reference height
• Liquid temperature
• Vapor temperature
• Air temperature
• Observed density value
• Average profile density
*
• Upper density
• Middle density
• Lower density
• P1 (bottom)
• P2 (middle)
• P3 (top)
• GP 1 value
• GP 2 value
• GP 3 value
• GP 4 value
Factory setting Water level
Additional information
Read access Operator
Write access Maintenance
The Measured level option doesn't contain a unit. If a unit is needed, select the Tank
level option.
Tertiary variable (TV)
Navigation Setup → Advanced setup → Communication → HART output → Configuration
→ Tertiary variable (TV)
Prerequisite Assign TV (→ 167) ≠ None
* Visibility depends on order options or device settings