Tankside Monitor NRF81 Operating menu
Endress+Hauser 173
Selection Normal
HTG
Factory setting Normal
Additional information
Read access Operator
Write access Maintenance
Tank reference height
Navigation  Setup → Advanced setup → Application → Tank configuration → Level → Tank
reference height
Description Defines the distance from the dipping reference point to the zero position (tank bottom or
datum plate).
User entry 0 to 100 000 mm
Factory setting Dependent on the device version
Additional information
Read access Operator
Write access Maintenance
Tank level
Navigation Setup → Advanced setup → Application → Tank configuration → Level → Tank level
Description Shows the distance from the zero position (tank bottom or datum plate) to the product
surface.
Additional information
Read access Operator
Write access -
Water level source
Navigation  Setup → Advanced setup → Application → Tank configuration → Level → Water level
source
Description Defines the source of the bottom water level.
Selection Manual value
Bottom level
HART device 1 ... 15 level
AIO B1-3 value