Operating menu Tankside Monitor NRF81
186 Endress+Hauser
Additional information
Read access Operator
Write access Maintenance
P3 position
Navigation  Setup → Advanced setup → Application → Tank configuration → Pressure → P3
position
Description Defines the position of the top pressure transmitter (P3), measured from zero position
(tank bottom or datum plate).
User entry 0 to 100 000 mm
Factory setting 20 000 mm
Additional information
Read access Operator
Write access Maintenance
P3 offset
Navigation  Setup → Advanced setup → Application → Tank configuration → Pressure → P3
offset
Description Offset for the top pressure (P3). The offset is added to the measured pressure prior to any
tank calculation.
User entry –2.5 to 2.5 bar
Factory setting 0 bar
Additional information
Read access Operator
Write access Maintenance
P3 absolute / gauge
Navigation  Setup → Advanced setup → Application → Tank configuration → Pressure → P3
absolute / gauge
Description Defines whether the connected pressure transmitter measures an absolute or a gauge
pressure.
Selection Absolute
Gauge
Factory setting Gauge