Operating menu Tankside Monitor NRF81
212 Endress+Hauser
User entry 0 to 3 000 kg/m³
Factory setting 800 kg/m³
Additional information
Read access Maintenance
Write access Maintenance
Density value
Navigation  Setup → Advanced setup → Application → Tank calculation → HTMS → Density value
Description Shows the calculated product density.
Additional information
Read access Operator
Write access -
Minimum level
Navigation  Setup → Advanced setup → Application → Tank calculation → HTMS → Minimum
level
Description Defines the minimum product level for a HTMS calculation. If Lp - V falls below the limit
defined in this parameter, the density retains its last value or the manual value is used
instead.
User entry 0 to 20 000 mm
Factory setting 7 000 mm
Additional information
Read access Operator
Write access Maintenance
Minimum pressure
Navigation  Setup → Advanced setup → Application → Tank calculation → HTMS → Minimum
pressure
Description Defines the minimum pressure for a HTMS calculation. If the pressure P1 falls below the
limit defined in this parameter, the density retains its last value or the manual value is
used instead.
User entry 0 to 100 bar
Factory setting 0.1 bar