Electrical
Connection
Ex i version
Ex d version
Multiple outputs 4...20 mA and Open Collector with intrinsically safe power supply
hazardous area
safe area
Intrinsically safe power supply
Stahl 9303/15-22-11
Switching repeater
Stahl 9250/05-10
Electronic
counter
Operation with HART handheld unit possible.
Minimum 250 load resistance needed for HART communication.
ti031y49
4...20 mA
Connection 4...20 mA or PFM current pulse
hazardous area
safe area
Note: 4...20 mA or PFM current pulse software selectable.
Open Collector not available with Ex d.
ti031y53
12...36 V DC
18.5...36 V DC
I
max
= 20 mA
4...20 mA
unscaled Vortex frequency 1...2850 Hz,
pulse width 0.18 ms
15