Measurement at a Glance
*Can be performed in reverse order
Function Matrix Action
1 Reset transmitter V9H5
● Enter 671: »+« and »–« keys, ⇒ changes digit
Press »E« to register entry
- Omit if commissioned as in Section 4.1
2 »Empty« calibration* V0H1
● Fill vessel 0…40% full (probe covered)
Enter level in %, m, ft, etc.
Press »E« to register entry
3 »Full« calibration* V0H2
● Fill vessel 60…100% full (probe covered)
Enter level in %, m, ft, etc.
Press »E« to register entry
4 0/4 mA signal V0H3
V0H5
V0H6
● Enter 0 for 0…20 mA signal, 1 for 4…20 mA signal
Press »E« to register entry
● Enter level for 0/4 mA signal (if not 0)
Press »E« to register entry
● Enter level for 20 mA signal (if not 100)
Press »E« to register entry
5 Relay 1 V1H0
V1H1
● Enter level for switching in calibration units, Relay 1
Press »E« to register entry
● Enter fail-safe mode: 0 = minimum, 1 = maximum
Press »E« to register entry
6 Relay 2 V1H5
V1H6
V1H9
● Enter level for switching in calibration units, Relay 2
Press »E« to register entry
● Enter fail-safe mode: 0 = minimum, 1 = maximum
Press »E« to register entry
● Enter 1 = Relay 2 assigned to channel 1
Press »E« to register entry
Silometer FMC 671 Z/676 Z Measurement at a Glance