4 Calibration and Operation
This chapter is concerned with the basic settings of the Silometer FMC 671 Z/676 Z which
allow it to operate for continuous level measurement. The principle sections describe:
Commissioning of the transmitter
Empty/full calibration for level measurement
Empty/full calibration for volume measurement
Level offset value
Display of measured values
Locking the parameter matrix.
The linearization for volume or weight measurements is described in Chapter 5, the
setting of the analogue outputs and relays in Chapter 6 and 7.
Note!
When configuring note your parameters in the Table in the rear cover.
If the transmitter is ever replaced, these parameters can be entered at the front
panel, with the FMC 671 Z, Commulog VU 260 Z or via the ZA 67 Gateway.
For level measurements, the transmitter will then measure correctly without the need
for another calibration, see Section 9.3.
4.1 Commissioning of the transmitter
If programming the module for the first time, reset the module to the factory based
parameters, see Table in back cover. Then enter the probe constants f
o
and S (f). This
ensures that the EC 37 Z/EC 47 Z electronic insert or Deltapilot can be replaced without
the need for recalibration, see Section 9.3.
Step Matrix Entry Significance
1 V9H5 e.g. 672 Enter any number 670
679 to reset transmitter
2 - »E« Register entry
3 V3H5 e.g. 475.3 Enter zero frequency f
o
(offset) of electronic insert with probe
4 - »E« Register entry
5 V3H6 e.g. 0.652 Enter sensitivity, S or
f, of electronic insert with probe
6 - »E« Register entry
Operating mode
Now select the operating mode at V8H0:
0 = continuous level measurement on channel 1 together with
level limit switching on channel 2, see Chapter 8, Section 8.3
1 = continuous level measurement on channel 1, Sections 4.2, 4.3
2 = level limit switching on channel 2, see Chapter 8, Sections 8.2
5 = measurement with calibration correction, see Chapter 8, Section 8.4
6, 7 =simulation channel 1 or 2, see Chapter 9, Section 9.2.
Step Matrix Entry Significance
1 V8H0 e.g. 1 Mode 1, continuous level measurement (default)
2 - »E« Register entry
Note!
The default settings for the Silometer are for % level measurement in operating
Silometer FMC 671 Z/676 Z Chapter 4: Calibration and Operation