mode 1. This corresponds to the calibration described in Section 4.2.
4.2 Empty/full calibration for level measurement
This calibration requires the determination of two parameters,
an »empty« level at V0H1,
a »full« level at V0H2.
After calibration
If the level is entered in %, after the calibration:
% level is displayed at V0H0
The 0/420 mA signal range corresponds to 0100% level
Limit relay 1 trips at 90% (maximum fail-safe)
the parameters »offset« and »sensitivity« are calculated and stored at
V3H1/V3H2.
If the level is entered in m, ft. etc. the analogue outputs and relay switching points must
be set in the same units, see Chapters 6 and 7.
Procedure
Step Matrix Entry Significance
1 V0H1 e.g. 10% Fill the vessel until the probe is covered (0
40%) and
enter the level you wish to have displayed.
2 - »E« Register entry
3 V0H2 e.g. 95% Fill the vessel as far as possible (60
100%) and
enter the level you wish to have displayed.
4 - »E« Register entry
5 V0H0 The measured value is shown in the units selected.
Note!
The calibration can be performed in reverse order
For bulk solids, the probe measures the depth of emersion in the product only.
Account for any filling mound or outflow depression by the entered levels.
»Full« V0H2
e.g. 95% or 5 m
BA063E27
Capacitance probe
Capacitance probe
»Empty«, V0H1
e.g. 10% or 0.5 m
Fig. 4.1:
Parameters required for
calibration of the Silometer
FMC 671 Z/676 Z for level
measurement shown for bulk
solid measurement.
Any filling mound or outflow
depression can be accounted for
by the parameters entered.