10.3 Level limit switching
Start
Chapter 8, Section 8.2
- Relay responds when the switch point
is exceeded or undershot
Calibration
Chapter 8, Section 8.2
Set relay parameters
Section 8.2
- Relay 1 can be assigned to channel 2
by entering = 2 at V1H4
Lock parameter matrix
Chapter 4, Section 4.6
Reset parameters: V9H5
Select mode V8H0
2 = Limit switching channel 2
Select sensor type V8H4
0 = Liquiphant
Set switching delay V8H2
Set fail-safe mode V1H1
0 = Minimum
1 = Maximum
Lock parameter matrix V8H9
Select sensor type V8H4
1 = Capacitance probe
Set switching point V8H6
1 = 1Hz, ca. 5 pF (default)
Calibrate V8H5
0 = probe uncovered
1 = probe covered
Press »E« to activate!!
Set switching delay V8H2
Set fail-safe mode V1H1
0 = Minimum
1 = Maximum
Lock parameter matrix V8H9
Capacitance probe
Liquiphant/
Soliphant
Silometer FMC 671 Z/676 Z Chapter 10: Quick programming guide