hours. Allow the battery to stand open circuit for a
minimum of 4 hours before repeating steps (iv) and (v).
viii.) If the second discharge duration is still less than 8
minutes, recharge the battery in accordance with
paragraph H and follow the rejection procedure.
b.) Option 2 – Using a 30 Amp discharge unit
i.) Check the battery open circuit voltage.
ii.) Perform a discharge as received test; discharge battery
to 21.0 volts and record the results.
iii.) Recharge the battery in accordance with paragraph H.
iv.) Allow the battery to stand open circuit voltage for 4 hours
minimum.
v.) Discharge the battery at 30 Amps to an end voltage of
21.0 volts.
vi.) If a discharge duration of 2 minutes or greater is
achieved, then the battery has passed the test.
Recharge the battery in accordance with paragraph H
and return to service.
vii.) If the discharge duration is less than 2 minutes, recharge
the battery in accordance with paragraph H for 12 – 24
hours. Allow the battery to stand open circuit for a
minimum of 4 hours before repeating steps (v) and (vi).
viii.) If the second discharge duration is still less than 2
minutes, recharge the battery in accordance with
paragraph H and follow the rejection procedure.
Page 16
Mar 13/17