www.enersys.com Publication No. US-RE-IOM-002 January 2012 Page 27
1.215
FLOAT
STEM
Periodically clean the hydrometer barrel and float with soap and water for ease of reading and
improved accuracy.
Specific gravity readings should be corrected for temperature. For every
3
o
F (1.67
o
C) of
temperature above
77
o
F (258
o
C), add one point (.001) to the hydrometer reading. For every 3
o
F
(1.67
o
C) of temperature below 77
o
F (25
o
C), subtract one point (.001) from the hydrometer
reading.