www.enersys.com Publication No. US-RE-IOM-002 January 2012 Page 19
7.3 Battery Installation
To install an EnerSys
®
battery system, follow the procedures below:
1. Clear area where battery will be placed, allow space for installation maneuvering.
2. Employ the appropriate lifting/handling method for the cells to be installed (as described in
Section 6.3).
Exercise extreme caution when initially lifting cells and when lowering them into final
position. To prevent one end of the unit from “kicking out,” assign one person to steady the
unit on a level plane during the entire lifting procedure.
3. After placement, carefully remove the lifting strap (if used) from the hook and pull the belt
from under the module.
WARNING
Improper lifting may result in damage to the module or
personal in
j
ur
y
.
WARNING
Do not allow steel crane parts or steel hooks of lifting straps to
come into contact with cell posts at any time. Allowing steel
lifting parts to contact cell terminals may results in a short.
WARNING
Allowing the cell/unit to drop quickly may damage the
internal cell components.