9.3 About the introduction of ‘Custom Setting’ mode,
‘Test’ mode, and ‘60Hz’ mode
• ‘CustomSetting’mode:Undercommonconditions,itisnotused,anditismainlyusedbysomespecial
customer to know the grid situation. When it is in this mode, customer can set the upper and lower
limits of voltage and eciency in a wide range to meet his requirements via software. Absolutely, it
is not modified randomly by customer because of the password protection, and we will provide the
password for customer.
• ‘Test’issetfortheproblemoffrequencyuctuationwhenitisaging,testasfollows:
- (1) Before T1 test, dial safety switch under common conditions, namely, where the machine is where it dial to.
- (2) After T1 test, before aging, turn the switch to aging mode.
- (3) After aging, before T2 test, turn the switch to common condition.
• ‘60Hz’modeisnotusedforthemoment.
Note: The switch should be set before power up, or it become invalid.
9.4 About the introduction of dierent safety standards
in dierent countries on LCD
Press the button ‘Function’, enter into the menu, you can see dierent countries with dierent safety
standards.WhenswitchrespectivelycorrespondstoGermany,Spain,Italy,60Hz,UK,Belgium,Custom
Setting and Test, and the menu shows as follows:
9.5 Mains voltage, eciency range and time reset
after disconnection
Country Reconnection
time (S)
Vmin(V) Vmax(V) Fmin (Hz) Fmax
(Hz)
VDE0126 – Germany/France/Bulgaria 30 187 262 47.51 50.19
RD1663 – Spain 180 198 250 49.01 50.99
DK5940 – Italy 30 187 262 49.7 50.3
G83–UnitedKingdom 180 209 262 47.01 50.49
Belgium – Belgium 30 198 253 47.5 50.5
Germany/France/Bulgaria Spain Italy 60Hz
UnitedKingdom Belgium Custom Setting Test