EasyManuals Logo

EngA G-TRAC 1.1 User Manual

Default Icon
23 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
A G-TRAC MANUAL
IOM-24 Page 16 March 1999 R1
Time (Jumpers) Time (Jumpers) Time (Jumpers) Time (Jumpers)
0:0 (1111)
0:15 (0111) 0:45 (1011) 1:15 (0011)
1:45 (1101)
2:15 (0101) 2:45 (1001) 3:15 (0001)
3:45 (1110)
4:15 (0110) 4:45 (1010) 5:15 (0010)
5:45 (1100)
6:15 (0100) 6:45 (1000) 7:15 (0000)
TO SET THE MAINTAIN PURGE TIME DELAY
Maintain Purge Time Delay is set by cutting the “maintain purge” jumpers on the back of the G-TRAC
board. This is best to do before installing a new board. Cut the same jumpers as were cut on the old
board or contact the factory (after getting unit serial number) for correct jumper information. Maintain purge
time is determined by the speed that heat exchangers lose heat and control systems react. If purge has
turned off and there is another call for heat, then pre-purge must occur again which may create wide
discharge temperature swings. Turning the combustion fan off is only done as an energy management
step.
JUMPER CONNECTIONS
APPLICATION
TIME IN
MINUTES
MP-1 MP-2 MP-3 MP-4
ONLY ROOM
CONTROL
0:30 CUT JUMPER JUMPER JUMPER
MOST
APPLICATIONS
6.30 CUT CUT CUT JUMPER
CTRAC
CONTROL
2:30 CUT CUT JUMPER JUMPER
Cutting all MP jumpers allows a "maintain purge" time of 12 minutes (plus or minus 2 minutes).
ESTIMATED POT SETTINGS (Use for situations where design values not available)
If the old G-TRAC is available, there was a sticker inside the cover showing the pot settings as they left
our factory. If this is not available and the control was operating well before it failed, then match the pot
settings. Failing that:
POT 5 Valve Sensitivity Set at 3 (or slightly lower)
POT 6 Internal Control Band set at 3 (If G-TRAC is slave to a CTRAC then set this at 4)
POT 8 Burner ON/OFF Control Band If G-TRAC is slave to a CTRAC then set this at 4
POT 4 Auxiliary Set point Usually not used. Used only if there is a jumper “SP to
S” (main set-point) or “SP to Y” (reset set-point)
POT 1 Discharge Calibration Must be set as per instruction in manual
POT 3 Room Calibration Must be set as per instruction in manual. This is usually
as a room or return air reset rather than as room control.
Used only if V, X, Y, Z are wired
POT 2 Room Reset Ratio Used only if POT 3 is used. Used to determine how
much authority will be given to the reset
thermostat/sensor. Setting 1 is the minimum authority
(+/- 9ºF) and setting 5 is the maximum authority (+/-
32ºF).
POT 7 BMS RESET RATIO Used only if there is a BMS control wired to the BMS
input terminals “+ and –“ (1 is minimum reset authority and
5 is maximum authority).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EngA G-TRAC 1.1 and is the answer not in the manual?

EngA G-TRAC 1.1 Specifications

General IconGeneral
BrandEngA
ModelG-TRAC 1.1
CategoryController
LanguageEnglish

Related product manuals