IQ 7 / IQ 7+ / IQ 7X / IQ 7A Installation and Operation
© 2020 Enphase Energy Inc. All rights reserved. 141-00044-02
IQ7A-72-2-INT Microinverter Parameters
Miscellaneous Parameters
Maximum9 microinverters per 20A (max) AC
branch circuit 230 VAC
11 (single-phase)
39 (multiphase, requires 25 A OCPD)
EN 50530 (EU) weighted efficiency
230 VAC (single phase)
%
96.5
Static MPPT efficiency (weighted, ref EN
50530)
%
99.5
Total harmonic distortion
%
5
Ambient temperature range
C
-40
+60
Night tare loss
mW
50
Storage temperature range
C
-40
+85
Features and Specifications
Compatibility
Pairs with most 60 and 72-cell PV modules
Dimensions not including mounting bracket
212 mm x 175 mm x 30.2 mm (approximate)
Connector type
Model IQ7A-72-2-INT: Bulkhead with MC4 locking type connector
Weight
1.08 kg (2.38 lbs.)
Environmental category / UV exposure rating
IP67 / outdoor
Torque specifications for fasteners
(Do not over torque)
6 mm mounting hardware: 5 N m
8 mm mounting hardware: 9 N m
When using earthing hardware, use the manufacturer’s
recommended torque value
Cooling
Natural convection no fans
Relative humidity range
4% to 100% condensing
Approved for wet locations
Yes
Pollution degree
PD3
Communication
Power line
Standard warranty term
enphase.com/warranty
Compliance
AS 4777.2, RCM, IEC/EN 61000-6-3, IEC/EN 62109-1,
IEC/EN 62109-2, EN 50549, G98/G99, VDE-AR-N-4105
Grounding
The DC circuit meets the requirements for ungrounded PV arrays.
Ground fault protection (GFP) is integrated into the class II double
insulated microinverter.
Monitoring
Enlighten Manager and MyEnlighten monitoring options require an
Enphase Envoy-S
Integrated DC disconnect
The DC connector has been evaluated and approved for use as the
load-break disconnect.
Integrated AC disconnect
The AC connector has been evaluated and approved for use as the
load-break disconnect.
9
Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area.
.