Troubleshooting an Enphase System
2014 Enphase Energy Inc. August 2014
42
3. In the clear-gfi menu, select set.
4. Click Send Command.
Grid Gone
The microinverter reports that power from the utility is no longer present or is out of voltage or frequency
specification. In most cases, no action is required. Solar production resumes when conditions normalize.
Enphase microinverters are utility interactive and require a connection to the utility.
Verify that the solar circuit breakers are on at the load center. If all breakers are on, the condition
should clear itself.
If Grid Gone events repeatedly occur on one microinverter or only on portions of a branch, call
Enphase Customer Support for assistance.
What is a “Utility Interactive” inverter?
The NEC (National Electric Code) defines this as, “An inverter intended for use in parallel with an
electric utility to supply common loads that may deliver power to the utility.” A utility-interactive
inverter lets PV system owners export excess power back to the utility.