30
Table 9: Orice and Pressure Information.
EX32 With Log Set & Proame Valve
Main Burner Natural Gas Propane Gas
Orice: #37 DMS #52 DMS
Max. Manifold Press: 3.6 W.C. (0.89 KPa) 10.0” W.C. (2.49 KPa)
Min. Manifold Press: 1.6 W.C. (0.40 KPa) 6.4” W.C. (1.59 KPa)
Max. Supply Press: 7.0” W.C. (1.74 KPa) 11.0” W.C. (2.74 KPa)
Min. Supply Press: 4.5” W.C. (1.12 KPa) 10.4” W.C. (2.59 KPa)
Max. Input: 32,500 BTU/hr (9.52 KW) 31,000 BTU/hr (9.08 KW)
Min. Input: 21,000 BTU/hr (6.15 KW) 24,500 BTU/hr (7.18 KW)
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
aDjusting the piLot fLame:
The pilot ow adjustment is set to maximum at the factory and should not need to be adjusted. The pilot
ame should envelope ⅜” to ½” (10 to 13mm) of the Flame sensor (see Figure 35). However, should the
need arise, follow Steps 1- 2 below.
1. The adjustment screw can be reached through the front of the unit using a 10 inch long blade head
screw driver (see Figure 34 for location on valve).
2. Turn the adjustment screw clockwise to decrease or counterclockwise to increase pilot ame.
Figure 35: Proper Pilot Flame.
Initial Installation
QUALIFIED INSTALLERS ONLY
.375
-.500
(10-13mm)
Flame Sensor