EasyManua.ls Logo

Envision R-410A - Troubleshooting

Envision R-410A
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
ENVISION RESIDENTIAL INSTALLATION MANUAL
Troubleshooting
Standard Microprocessor Controls
To check the unit control board for proper operation:
1) Disconnectthermostatwiresatthecontrolboard.
2) Jumperthedesiredtestinput(Y1,Y2,W,OorG)totheRterminaltosimulateathermostatsignal.
3) If control functions properly:
• Checkforthermostatandeldcontrolwiring(usethediagnosticinputsmode).
4) Ifcontrolrespondsimproperly:
• Ensurethatcomponentbeingcontrolledisfunctioning(compressor,blower,reversingvalve,etc.).
• Ensurethatwiringfromcontroltothecomponentisfunctioning(refertotheLEDDenitiontablebelowandusethe
diagnostic outputs mode).
• Ifstepsabovecheckproperly,replaceunitcontrol.
Refrigerant Systems
To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Compare the
changeintemperatureontheairsideaswellasthewatersidetothetablesonpages35-36.Iftheunit’sperformanceisnot
withintherangeslisted,andtheairowandwaterowareknowntobecorrect,gaugesshouldthenbeinstalledandsuper-
heat and subcooling numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to
the refrigerant charge may be necessary.
Note:
Refrigerant tests must be made with desuperheater turned “OFF”.
Verifythatairandwaterowratesareatproper
levels before servicing the refrigerant circuit.
LED
NORMAL
DISPLAY MODE
DIAGNOSTIC MODES
CURRENT
FAULT STATUS
INPUTS OUTPUTS 1 OUTPUTS 2
Field Selection DIPS
SW2- 1On SW2- 1Off SW2- 1NA SW2- 1NA SW2- 1NA
SW2- 6On SW2- 6On SW2- 6Off SW2- 6On SW2- 6Off
SW2- 7On SW2- 7On SW2- 7On SW2- 7Off SW2- 7Off
Drain
DrainPanOverow
Lockout
DrainPanOverow Y1
Compressor
(On or Low)
Blower
Low
Water Flow
FP Thermistor (Loop
<15ºF,Well<30ºF)
Lockout
FP Thermistor (Loop
<15ºF,Well<30ºF)
Y2
Compressor
(On or High)
Blower
Medium
High
Pressure
HighPressure>600
PSI Lockout
HighPressure>600 O Reversing Valve
Blower
High
Low
Pressure/
Compressor
LowPressure<40
PSI Lockout or
Comfort Alert
LowPressure<40
or Comfort Alert
G Fan AuxHeat1
Airow
ECM2RPM<100
RPM
ECM2RPM
<100RPM
W DHW Pump AuxHeat2
Status
Microprocessor
Malfunction
Not Used SL1 Loop Pump(s) Aux Heat 3
DHW Limit
HWL Thermistor
>130º
HWL Thermistor
>130°F
Not Used AuxHeat4
DHW Off
DHW Pump
Switch Off
DHW Pump
Switch Off
LED Denitions and Diagnostics
Standard Microprocessor

Other manuals for Envision R-410A