Room Thermostat CP4
V2
P0 1 Operating Mode Normal
There are three settings for selection, Normal, Optimum Start or TPI mode.
The default setting is Normal.
Press and hold
PROG
and for 5 seconds.
‘P01 & Nor’ will appear on the screen.
Press
to select.
Press
or to select between:
Nor (Normal mode)
OS (Optimum start)
TPI (Time Proportion Integral mode)
Press
to conrm the mode.
Press
AUTO
to return to normal operation.
Nor (Normal Mode)
When the thermostat is in Normal mode, the thermostat will try to reach the
target temperature at the program time.
Example: Program 1 on the thermostat is 21°C for 06:30am and the room
temperature is 18°C. The thermostat will start the heating at 06:30am and
the room temperature will start to increase.