Room Thermostat CP4
V2
This menu allows the installer to change the switching dierential of the
thermostat when the temperature is rising and falling.
If ‘H On’ is set at 0.4°C and the setpoint is 20°C, then the thermostat will
turn on when the temperature drops below 19.6°C.
If ‘H OFF’ is set at 0.0°C and the setpoint is 20°C, then the thermostat will
turn o when the temperature reaches 20°C.
Press and hold
PROG
and for 5 seconds.
‘P01’ will appear on the screen.
Press
until ‘P03 & H On’ appears on the screen.
Press
to select.
‘H On’ temperature will begin to ash.
Press
or to adjust the ‘H On’ temperature between 0.2°...1°C.
Press
to conrm.
‘H OFF’ temperature will begin to ash.
Press
or to adjust the ‘H OFF’ temperature between 0.0°...1°C.
Press
AUTO
once to return to the menu or twice to return to normal
operation.
P0 3 Hysteresis HOn and HOFF HOn 0.4˚C and HOFF 0.0˚C