39
RFRP
V2
Room Thermostat CP4
V2
P0 4 Calibrate the thermostat
This function allows the user to calibrate the temperature reading of
the thermostat.
Press and hold
PROG
and for 5 seconds.
‘P01’ will appear on the screen.
Press
until ‘P04 & CAL’ appears on the screen.
Press
to select.
The current actual temperature will appear on screen.
Press
or to adjust the temperature reading.
Press
to conrm and you will return to the menu.
Press
AUTO
to return to the home screen.
P0 3 Hysteresis HOn and HOFF HOn 0.4˚C and HOFF 0.0˚C