The IPES‐IR3 meets industry certifications and requirements for Hazardous Locations.
Detection Type: Optical
Detection Method: Multiple Spectrum Infrared Radiation Source Spectral Range: Three points in a range of 4.0 to 5.0 m
Detection Process Time:
4.5 to 7 Seconds
(Complies with FM Standard 3260)
Refer to Section 4.0
Detection Distance: Minimum 211 feet (64meters) depending on detected fuel.
Detection Cone of Vision: Up to 90° (45° Left/Right of center)
Sensitivity: User Selectable for distance and False/Positive process time
Power requirements: 24VDC nominal (18‐32VDC range)
Power Consumption: 3 VA (3 Watt) Max
Outputs:
● Industry Standard +4 to 20mA
● 1 Alarm Relays (SPDT/Form‐C latching)
● 1 Fault condition (NO/Form‐A)
*All Relays Contact Rating 1 Amp@125VAC/30VDC
● Digital RS‐485 Modbus
● HART Communication Protocol
Cable Distance: 6200ft (1900m) 18 AWG
Ingress Protection: IP66
Vibration: Meets FM 3260: 2000
Impact Resistance: 1.9 Joules
Test Method: ITES Test Lamp
RFI‐resistant to interference by EMI and RFI: EMC Directive compliant with CE mark. Not susceptible to keying 5 watt
walkie‐talkie at distances greater than 1 foot.