IPES IR3 Flame Detector
Operating Manual
Page 9 of 37
4.0 FM Compliance
Meets FM (US and Canada) certifications and requirements for Hazardous Location classification: Class I, Division I,
Group B, C and D and T4 Case design accords with FM 3600 and FM 3615. Ta = ‐40°C to +85°C (‐40°F to +185°F) IP66
Radiant Energy‐Sensing Fire
Detectors for Automatic Fire
Alarm Signaling
Radiant Energy‐Sensing Fire
Detectors for Automatic Fire
Alarm Signaling
Electrical Equipment For Use In
Hazardous (Classified) Locations –
General Requirements
Explosion proof Electrical
Equipment – General
Requirements
Standard for Smoke Detectors for
Fire Alarm Systems
Explosion‐Proof Enclosures for
Use in Class I Hazardous Locations
Degrees of Protection Provided by
Explosive Atmospheres, General
Requirements
Explosive Atmospheres,
Equipment protection by
flameproof “d” enclosures
Flame Response
Sensitivity
When an IPES‐IR3 detector is exposed to a series of test fires along the center line of the sensor as described in the table
below, the alarm response of the IPES‐IR3 is below the 30‐ second response time required under FM Standard 3260.
1 ft. x 1 ft. (32.5 cm.) pan
Denatured ethyl
alcohol (85.4%)
2 ft. x 2 ft. (60 cm.) pan