EasyManua.ls Logo

Epsolar ET2415N - Page 44

Epsolar ET2415N
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 40
Table 8.1: Parameter for 12V system
Multiplied 2,3 and 4 respectively for 24V ,36V and 48V system
Item
Default
Options & Range
1
Batt Type
SEALED
GEL, SEALED , FLOODED
2
Batt Rated Volt
12.0 V
12.0,24.0,36.0,48.0 V
3
Over Volt. Disc
16.0 V
15.0~17.0 V
4
Over Volt. Rect
15.0 V
14.0~16.0 V
5
Charging Limit
15.5 V
14.0~16.0 V
6
Equalize Charge
GEL
--
14.2~15.2 V
SEALED
14.6 V
FLOODED
14.8 V
7
Boost Charge
GEL
14.2 V
13.8~15.0 V
SEALED
14.4 V
FLOODED
14.6 V
8
Float Charge
13.8 V
13.2 ~14.2 V
9
Boost Volt. Rect
13.2 V
12.7~13.5 V
10
Under Volt.Warn
12.2 V
11.8 ~12.6 V
11
Low Volt. Rect
12.6 V
12.0~13.2 V
12
Low Volt. Disc
11.1 V
10.5~11.8 V
13
Discharge Limit
10.8 V
10.5~11.0 V
14
Equalize Time
GEL
--
GEL
--
SEALED
120 Min
SEALED
0~180
Minutes
FLOODED
FLOODED
15
Boost Time
120 Minutes
0~180 Minutes
16
Temp Coefficient
-5mV//2V
- 9~0mV//2V
Notes:
This parameter be detected auto by controller, user cant set it.
Equalize charge interval is 28 days. No matter when LVD happens within 28 days.

Other manuals for Epsolar ET2415N