Captair Flow Smart
Mobile ductless ltering clean air enclosure
20
When reassembling the ltration column, be sure that the fan module is positioned correctly to access your connection points.
ExamplE: Captair Flow 483 Smart
ExamplE: Captair Flow 321 Smart
A i r Fl o w
Reconnect the power supply to the fan
Recommendations for storing and using the filters
New lter shelf life and storage conditions:
New activated carbon molecular lters must be stored at in their original packaging at a temperature of between +10°C / 50°
F and +50°C / 120° F and a humidity level < 85% RH.
HEPA H14 and/or ULPA lters must be stored upright and kept dry.
If these conditions are respected, the maximum time a lter can be stored before use depends on the type of lter:
AS type carbon molecular lter 1 year from the date of delivery
HEPA/ULPA lter 2 years from the date of delivery
If the maximum shelf life is reached, we recommend not to install lters.
Filters replacement frequency
Prelters(s) should be replaced every year.
HEPA/ULPA lters should be replaced every 3 years on average.
Molecular lter should be replaced every 2 years on average.