? Fault code U. and 2 flash alternately and the
light is red?
! Voltage supply is above the limit (programmable
limit, e.g. >260V).
Ensure that adequate mains voltage is supplied.
? Fault code U. and 3 flash alternately and the
light is red?
! All start-up attempts in the programmed voltage
range (e.g. 160 180V) are unsuccessful. The
last start-up attempt is not made to prevent a
lock-out.
Ensure that adequate mains voltage is supplied.
? Fault code U. and 5 flash alternately and the
light is red?
! While a fault was pending, the unit has been
successfully reset more than 5 times within
15minutes using the remote reset input.
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
? Fault code U. and 6 flash alternately and the
light is red?
! The unit has been unsuccessfully reset more
than 10times within 15minutes using the remote
reset input.
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
? A circulating dash is displayed rather than
a fault code?
After switching on the voltage, a circulating dash
is displayed.
Three possible pieces of information are output:
! Switch-on delay time running.
Or
! Cycle lock active. The time (cycle lock) between
two starts is too short.
The display will go out automatically as soon as
the time between two starts is long enough. The
burner control unit will ensure a pause between
start-up attempts on the basis of its parameteri-
zation. This warning is displayed during this time.
Or
! The main fan is switched off but the pressure
switch signal does not drop. A burner restart is
not possible.
After 25s, the display will change to fault code
A. 9.