EasyManua.ls Logo

EST LSRA - Hardware Installation

EST LSRA
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
Hardware Installation
The LSRA(-C) mounts on a 4” square electrical box.
Refer to Figure Chapter 3-1
1. Install the mounting ring (P/N P-039964-1243) on the electrical
box, as shown in panel A.
2. Install the LSRA-232 Printer/Programming Port board in the
annunciator, if used. Refer to Figure Chapter 3-8.
3. Wire the annunciator. Refer to the appropriate wiring diagrams in
the wiring section.
4. Slide the top of the annunciator on the top flange of the mounting
ring, then push the bottom of the annunciator over the stud-nut, as
shown in panel B.
5. Secure the bottom of the annunciator to the adapter ring using the
screw provided, as shown in panel C. Cover the screw hole with the
label provided.
A
BC
[xmdnmtg.cdr]
Figure Chapter 3-1: Installation Procedure, LSRA(-C)
LSRA Installation, Operation, Maintenance, and Configuration Manual 3.3
firealarmresources.com