Pr06 0 9 - - - - 0 Manufact.
enabling mode
0 = from digital input DI1 or DI2
(stand alone)
1 = from digital input DIHV (stand
alone)
2 = from CANBUS
3 = reserved
4 = from serial MS RS-485
5 = reserved
6 = from CANBUS + DI1 or DI2 as
consequence of communication
error
7 = reserved
8 = from serial MS RS-485 + DI1 or
DI2 as consequence of
communication error
9 = reserved
Pr08 0 255 s 1 Installer stabilization delay
Pr09 0.00 100.00 % 50.00 Installer stabilization position
Pr20 0.00 100.00 % 0.00 Installer stand-by position
Pr30 50.00 100.00 % 100.00 Manufact. limit valve opening
Pr40 0 9999 h 0 User working hour (read only parameter)
Pr41 0 365 day 1 Installer
resynchronization interval
0 = disabled
Pr45 30 100 % 100 Manufact. reserved
Pr48 0.00 100.00 % 0.00 Installer communication error position
Par. Min. Mas. Unità Default Menu Valve and driver: generic valve
Pr50 0 Pr51 step 200 Manufact. minimum regulation steps
Pr51 Pr50 9999 step 1596 Manufact. maximum regulation steps
Pr52 Pr51 9999 step 1600 Manufact. overdrive steps
Pr53 25 1000 step/s 200 Manufact. stepping rate
Pr54 0 1000 mA 120 Manufact. operating phase current
Pr55 0 1000 mA 0 Manufact. holding phase current