EVCO S.p.A. EVDRIVE03 | User manual ver. 3.7 | Code 144EPDE374
Page 42 of 76
Ph21 0 4 - - - - 2 Manufact.
free of voltage digital input DI2 function
0 = none
1 = enable/disable valve
2 = change parameters set
3 = resynchronization request
4 = backup battery status
Ph30 0 1 - - - - 0 Manufact.
high voltage digital input logic
0 = normally open
1 = normally closed
Ph31 0 4 - - - - 0 Manufact.
high voltage digital input DIHW function
0 = none
1 = enable/disable valve
2 = change parameters set
3 = resynchronization request
4 = backup battery status
Ph60 0 1 - - - - 0 Manufact.
pressure unit of measurements
0 = barG
1 = psiG
Ph61 0 1 - - - - 0 Manufact.
temperature unit of measurements
0 = °C / K
1 = °F / R
Ph70 0 1 - - - - 0 Manufact.
frequency grid
0 = 50 Hz
1 = 60 Hz
Ph80 0 2 - - - - 0 Manufact.
LED “STEP 2” function
0 = status
1 = LOP alarms + MOP alarms
2 = Lo SH alarms + Hi SH alarms
Par. Min. Mas. Unità Default Menu Probe settings: analog input AI1
Piu1 0 4 - - - - 1 Manufact.
analog input AI1 function
0 = not used
1 = suction temperature backup probe
2 = suction pressure backup probe