EVCO S.p.A. EVJ800 | Installer manual ver. 1.0 | Code 144J800E104
page 33 of 48
d3 30 0 99 min
If the evaporator probe is not present (P4=0), it sets the
defrost duration
If the evaporator probe is present (P4=1), it sets the maximum
defrost duration. See also parameter d2
0 = defrost is never activated
d4 0 0 1 - - - -
Enable defrost at the start of blast chilling and of blast freezing
0 = no
1 = yes
d5 30 0 99 min
Defrost delay from the beginning of conservation
0 = defrost starts as soon as conservation is started and is
repeated in accordance with parameter d0
d7 2 0 15 min
Drip time after a defrost, in which the compressor and the
evaporator fan are switched off and the defrost output is
deactivated
d15 0 0 99 min
Minimum consecutive compressor-on duration for starting hot
gas defrost, if d1 is set to 1
d16 0 0 99 min
Pre-drip time if d1 is set to 1 (hot gas defrost), in which the
compressor and the evaporator fan are off and the defrost
output remains activated
PAR. DEFAULT
MIN. MAX. U.M. TEMPERATURE ALARMS
A1 10 0 99 °C
Cabinet temperature below which the minimum temperature
alarm is activated (relative to the working setpoint, i.e. “r10–
A1” during conservation after blast chilling and “r11–A1” during
conservation after blast freezing (“LOW TEMPERATURE
code);
see also parameter A11
A2 1 0 1 - - - -
Enable minimum temperature alarm (“LOW TEMPERATURE
code):
0 = no
1 = yes
A4 10 0 99 °C
Cabinet temperature above which the maximum temperature
alarm is activated (relative to the working setpoint, i.e.
“r10+A4” during conservation after blast chilling and r11+A4”
during conservation after blast freezing (“HIGH
TEMPERATURE” code);
see also parameter A11 (4)
A5 1 0 1 - - - -
Enable maximum temperature alarm (“HIGH TEMPERATURE
code):
0 = no
1 = yes
A7 15 0 240 min
Temperature alarm delay (“HIGH TEMPERATURE code and
LOW TEMPERATURE” code)