EVCO S.p.A. EVJ800 | Installer manual ver. 1.0 | Code 144J800E104
page 38 of 48
9 ALARMS
9.1 Alarms
The alarms will be displayed on the Home page if the effect is to interrupt or to prevent the activation of the cycle. If
they are such as to allow the continuation of the cycle in progress they will instead take the place of the "cycle
progress bar" until they disappear.
The table below lists the various alarms.
Code Description
RTC
Clock error.
To correct:
- re-set the date and time.
Main results:
- the device will not save the date and time an HACCP alarm occurred.
- the alarm output will be activated.
CABINET PROBE
Cabinet probe error.
To correct:
- check the value of parameter P0
- check the integrity of the probe
- check the device-probe connection
- check the cabinet temperature.
Main results:
- if the error occurs during “stand-by”, it will not be possible to start up an operating
cycle
- if the error occurs during blast chilling or blast freezing, the cycle will continue with the
compressor in continuous mode
- if the error occurs during conservation, the compressor will operate according to
parameters C4 and C5 or C9
- if the error occurs during a thawing cycle, the cycle will be interrupted
- the minimum temperature alarm will never be activated
- the maximum temperature alarm will never be activated
- the door heaters will never be switched on
- the alarm output will be activated