EasyManuals Logo

Evco EVJ 800 series User Manual

Evco EVJ 800 series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
EVCO S.p.A. EVJ800 | Installer manual ver. 1.0 | Code 144J800E104
page 36 of 48
u2 2 0 3 - - - -
Load managed by output K5
0=cabinet light
1=UV lamp
2= needle probe heater
3=alarm
u5 2 -50 99 °C
Cabinet temperature over which the door heaters are switched
off
u6 5 1 240 min Time the UV lamp is on for the sterilisation cycle
u7 40 -50 199 °C
Temperature to end needle probe heating;
see also parameter u8
u8 2 0 240 min
Maximum duration of needle probe heating;
see also parameter u7
0 = needle probe heating is disabled
u11 0 0 1 - - - -
Enable evaporator ventilation during sterilisation (only valid if
u1=1)
0=no
1=yes
PAR. DEFAULT
MIN. MAX. U.M. SECURITY AND EVLINK DATA-LOGGING
Hr0 1 0 1 - - - -
Enable clock
0 = no
1 = yes
Loc - - - - - - - - - - - - - - - - Unused
PA1 426 -99 999 - - - - EVCONNECT APP level 1 password
PA2 824 -99 999 - - - - EVCONNECT APP level 2 password
rE0 5 1 240 min
EVLINK data recording interval during blast chilling, blast
freezing, ice cream hardening and fish sanitation
rE1 1 0 2 - - - -
Selection of values sampled by BLE data logger
0 = none
1 = HACCP data (cabinet temperature, needle, cycle duration,
type of cycle, total blast chilling time, HACCP alarms)
2 = SERVICE data (all temperatures, all events, all alarms, all
cycles)
bLE 1 0 1 - - - -
Activate Bluetooth
0 = no
1 = yes
PAR. DEFAULT
MIN. MAX. U.M. MODBUS
LA 247 1 247 - - - - Device address

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Evco EVJ 800 series and is the answer not in the manual?

Evco EVJ 800 series Specifications

General IconGeneral
BrandEvco
ModelEVJ 800 series
CategoryController
LanguageEnglish

Related product manuals