EVCO S.p.A. EVJ800 | Installer manual ver. 1.0 | Code 144J800E104
page 36 of 48
u2 2 0 3 - - - -
Load managed by output K5
0=cabinet light
1=UV lamp
2= needle probe heater
3=alarm
u5 2 -50 99 °C
Cabinet temperature over which the door heaters are switched
off
u6 5 1 240 min Time the UV lamp is on for the sterilisation cycle
u7 40 -50 199 °C
Temperature to end needle probe heating;
see also parameter u8
u8 2 0 240 min
Maximum duration of needle probe heating;
see also parameter u7
0 = needle probe heating is disabled
u11 0 0 1 - - - -
Enable evaporator ventilation during sterilisation (only valid if
u1=1)
0=no
1=yes
PAR. DEFAULT
MIN. MAX. U.M. SECURITY AND EVLINK DATA-LOGGING
Hr0 1 0 1 - - - -
Enable clock
0 = no
1 = yes
Loc - - - - - - - - - - - - - - - - Unused
PA1 426 -99 999 - - - - EVCONNECT APP level 1 password
PA2 824 -99 999 - - - - EVCONNECT APP level 2 password
rE0 5 1 240 min
EVLINK data recording interval during blast chilling, blast
freezing, ice cream hardening and fish sanitation
rE1 1 0 2 - - - -
Selection of values sampled by BLE data logger
0 = none
1 = HACCP data (cabinet temperature, needle, cycle duration,
type of cycle, total blast chilling time, HACCP alarms)
2 = SERVICE data (all temperatures, all events, all alarms, all
cycles)
bLE 1 0 1 - - - -
Activate Bluetooth
0 = no
1 = yes
PAR. DEFAULT
MIN. MAX. U.M. MODBUS
LA 247 1 247 - - - - Device address