EVCO S.p.A. EVJ800 | Installer manual ver. 1.0 | Code 144J800E104
page 41 of 48
SANITATION
PROBE
INSERTION
Sanitation alarm.
To correct:
- check that the needle probe has been correctly inserted and check the value of
parameters r17 and r18.
Main results:
- the sanitation cycle will be interrupted.
SANITATION
DURATION
Alarm indicating that sanitation has not been completed within the maximum duration of the
first phase.
To correct:
- check the value of parameter r23
Main results:
- the device will save the alarm
- the cycle underway will be interrupted
- the alarm output will be activated
CONDENSER
OVERHEATING
Condenser overheat alarm.
To correct:
- check the condenser temperature
- check the value of parameter C6.
Main results:
- the condenser fan will be switched on
- the alarm output will be activated
COMPRESSOR
LOCKED
Compressor locked alarm.
To correct:
- check the condenser temperature
- check the value of parameter C7
- disconnect the device from the power supply and clean the condenser.
Main results:
- if the error occurs during “stand-by”, it will not be possible to select or start up an
operating cycle
- if the error occurs during an operating cycle, the cycle will be interrupted.
- the alarm output will be activated
NEEDLE PROBE
INSERTION
Needle probe not inserted alarm.
To correct:
- check that the needle probes have been correctly inserted and check the value of
parameters r17 and r18.
Main results:
- the temperature controlled cycle in progress will be converted to a time controlled
cycle.