EVCO S.p.A. EVJ800 | Installer manual ver. 2.0 | Code 144J800E204
page 38 of 50
rE1 1 0 2 - - - -
Selection of values sampled by EVLINKING
0 = none
1 = HACCP data (cabinet temperature, needle, cycle duration,
type of cycle, total blast chilling time, HACCP alarms)
2 = SERVICE data (all temperatures, all events, all alarms, all
cycles)
bLE 1 0 99 - - - -
Serial port connectivity configuration
0 = free
1 = forced for EVconnect or EPoCA
2-99 = EPoCA local network address
PAR. DEFAULT
MIN. MAX. U.M. MODBUS
LA 247 1 247 - - - - Device address
Lb 3 0 3 - - - -
Baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
LP 2 0 2 - - - -
Parity
0 = none
1 = odd
2 = even
PAR. DEFAULT
MIN. MAX. U.M. VARIOUS
E13 1 0 1 - - - -
Machine configuration: (only available in model EVJ825)
0 = Blast chilling
1 = Blast chilling and blast freezing