EVCO S.p.A. EVJ800 | Installer manual ver. 2.0 | Code 144J800E204
page 37 of 50
PAR. DEFAULT
MIN. MAX. U.M. DIGITAL OUTPUTS
u1 1 0 2 - - - -
Load managed by output K4
0=door frame heater
1=condenser fan
2=thawing heater
u2 2 0 3 - - - -
Load managed by output K5
0=cabinet light
1=UV lamp
2= needle probe heater
3=alarm
u5 2 -50 99 °C
Cabinet temperature over which the door heaters are switched
off
u6 5 1 240 min Time the UV lamp is on for the sterilisation cycle
u7 40 -50 199 °C
Temperature to end needle probe heating;
see also parameter u8
u8 2 0 240 min
Maximum duration of needle probe heating;
see also parameter u7
0 = needle probe heating is disabled
u11 0 0 1 - - - -
Enable evaporator ventilation during sterilisation (only valid if
u1=1)
0=no
1=yes
PAR. DEFAULT
MIN. MAX. U.M. SECURITY AND EVLINKING DATA-LOGGING
Hr0 1 0 1 - - - -
Enable clock
0 = no
1 = yes
Loc - - - - - - - - - - - - - - - - Unused
SEn 70 60 120 - - - - Key sensitivity setting
PAS -19 -99 999 - - - -
Password setting for parameter editing
Regardless the value set, access to parameter editing is always
enabled by the superpassword 743
PA1 426 -99 999 - - - - EVconnect/EPoCA level 1 password
PA2 824 -99 999 - - - - EVconnect/EPoCA level 2 password
rE0 5 1 240 min
EVLINKING data recording interval during blast chilling, blast
freezing, ice cream hardening and fish sanitation