F33 0 0 1 - - - -
Fan operating mode during fifth phase of thawing:
0 = in parallel with the compressor and thawing heater
1 = always on
F46 15 0 99 °C
Condenser temperature above which the condenser fan is
switched on
F47 30 0 240 s
Condenser fan switch-off delay from when the compressor is
switched off (only if the condenser probe is not present)
F48 0 0 1 - - - -
Condenser fan status during defrosting
0 = off
1 = on
F49 0 0 2 - - - -
Fan operating mode during conservation
0 = in parallel with the compressor
1 = always on
2 = cyclical with compressor off (only available in model
EVJ825)
PAR. DEFAULT
MIN. MAX. U.M. DIGITAL INPUTS
i0 2 0 2 - - - -
Effect of the door opening, or when the door switch input is
activated
0 = no effect and no signal
1 = the compressor, evaporator fan, thawing heaters, heater
and humidifier are switched off and the cabinet light is
on, once the time set by parameter i2 has elapsed, the
device displays the alarm and the buzzer is activated
until the door is closed. See also parameter F15
2 = the evaporator fan is switched off and the cabinet light is
on, once the time set by parameter i2 has elapsed, the
device displays the alarm and the buzzer is activated
until the door is closed. See also parameter F15
i1 0 0 1 - - - -
Door switch input polarity
0 = normally open (input active with contact closed)
1 = normally closed (input active with contact open)
i2 5 -1 120 min
Door open duration for recording open door alarm and
deactivating all outputs except light and alarm;
-1 = alarm not signalled
i5 0 0 2 - - - -
Function linked to multi-purpose digital input:
0 = high pressure switch
1 = low pressure switch
2 = compressor thermal switch
i6 0 0 1 - - - -
Multi-purpose input polarity
0 = normally open (input active with contact closed)
1 = normally closed (input active with contact open)
i7 5 -1 240 s
Multi-purpose alarm signalling delay
-1 = alarm not signalled