EVCO S.p.A. EVJ800 | Installer manual ver. 2.0 | Code 144J800E204
page 35 of 50
A8 15 0 240 min
Maximum temperature alarm delay ("HIGH TEMPERATURE"
code) from the start of conservation
A10 5 0 240 min
Power failure duration sufficient for the power failure alarm to
be saved (“POWER FAILURE” code) when this is restored
0 = alarm not signalled
A11 2 1 15 °C Parameter A1 and A4 differential
A12 5 0 240 s
Duration of buzzer activation on completion of blast chilling and
blast freezing
A13 60 0 240 s Duration of alarm buzzer activation
PAR. DEFAULT
MIN. MAX. U.M. EVAPORATOR AND CONDENSER FANS
F1 -1 -50 99 °C
Evaporator temperature above which the evaporator fan
switches off during pre-cooling/blast chilling/blast
freezing/sanitation/ice cream hardening
see also parameter F8
F3 2 0 15 min
Duration of evaporator fan-off time (while the evaporator fan is
off the compressor may be switched on, the defrost output is
de-activated and the evaporator fan stays off)
F7 -1 -50 99 °C
Evaporator temperature below which the evaporator fan
switches on after dripping (only available in model EVJ825)
F8 2 1 15 °C Parameter F1 and F17 differential
F15 15 0 240 s
Evaporator fan delay from when the door is closed, or the door
switch input is deactivated
F17 90 -50 199 °C
Cabinet temperature above which the evaporator fan switches
off during pre-cooling/blast chilling/blast freezing/sanitation/ice
cream hardening;
see also parameter F8
F18 30 0 240 s
time evaporator fan on in conservation while the compressori is
off (only available in model EVJ825)
F19 120 0 240 s
time evaporator fan off in conservation while the compressori is
off (only available in model EVJ825)
F29 0 0 1 - - - -
Fan operating mode during first phase of thawing:
0 = in parallel with the compressor and thawing heater
1 = always on
F30 0 0 1 - - - -
Fan operating mode during second phase of thawing:
0 = in parallel with the compressor and thawing heater
1 = always on
F31 0 0 1 - - - -
Fan operating mode during third phase of thawing:
0 = in parallel with the compressor and thawing heater
1 = always on
F32 0 0 1 - - - -
Fan operating mode during fourth phase of thawing:
0 = in parallel with the compressor and thawing heater
1 = always on