42
ABF 05-10-15
ENGLISH
Blast Hard Cycle
The display DIS1 shows up the core probe temperature in case of temperature cycles, or the temperature of the probe
cold room in cycles set’ it in modality “time”.
The display DIS2 visualizes the time in decrease in both kinds, temperature or time cycles.
The time used for the temperature cycles is determinate by the value of the parameter.
To Temperature modality cycles, the reduction of the cycles start only if the core probe temperature is under the value
set’ it .
To Temperature modality cycles, the decrease of the cycles starts only if the core probe temperature is under the value
settled.
The hard led is on
, during the first phase, wile in the second blinking.
The pressure of the key Decrement
allows to visualize on DIS2 the time spent by the beginning of the cycle.
During a temperature cycle is possible view the core probe temperature cold room, press the key HARD visual-
ization remains on the displays for five seconds.
During a time cycle is possible view the core probe temperature cold room, press the key TEMPERATURE
visu-
alization remains on the displays for five seconds.
When the temperature of the core probe reach the value set’ it for a time cycle or expires the time set for a time cycle,
the first phase ends and automatically stars the second phase, that once reached the temperature chosen or the time
set’ it expires, the buzzer plays and it starts the maintenance phases.
To switch of the buzzer press the key less
(decrease).
During the maintenance phases, press the key Less
(decrease) to see the all complete during of the Hard
phases.
To see the core probe temperature, press the Key Core Probe
, the value remain on the displays for five sec-
onds
NOTE: if the probe core don’t reach the set point within the defined time, the display DIS2 blinks on and the cycle con-
tinues until the set point reach.
CONTROL OF THE CORE INSERT
During a temperature cycle a test is made to verify the correct insertion of the probe core in the product.
The test is articulated in two steps.
The first step verifies for five times the difference of temperature between the probe core and the probe cold room, if for
three times the difference is highest to the value of the parameter, the probe core is considered inserted correctly and
the second step don’t have to be performed.
If, instead, the result of the first phase is negative, the second step must be performed on the fact that the temperature
in the cold room goes down more quickly that the temperature inside the product. At this point check that the difference
of temperature between the outside and the inside increases.
If the result of the second test is positive the program continues normally and the core probe is considered inserted cor-
rectly on the product.
If the result of the second test is negative, the led Temperature
, for the blast chiller soft and hard cycles or the led
Freezing Temperature
, blinking and the buzzer plays in intermittent
(5 brief beeps and one of break of 10 seconds).