ABF 05-10-15
ENGLISH
ALARMS
Each alarm is evidence by the sound of the buzzer, that can be turn off with the key Decrement
.
Otherwise the buzzer goes on for a definite time.
NOTE: If there’s sterilization in progress, the defined delay is not respected. In the case both in progress a heating hat
probe core, the opening of the door doesn’t implicate any signaling of alarm.
Alarm Probe Cold Room
It appears, when notified a problem in the probe cold room. The display visualize the label “Er0” and if there’s a cycle is
in progress, will be immediately interrupt. The buzzer plays.
The start on is automatic in condition of alarm disappeared.
Evaporator Probe Alarm
Appears if notified problem of probe evaporator. The display visualize the label “Er1.” The buzzer plays.
The alarm doesn’t have effect on a cycle of blast, while if a maintenance is in progress the evaporator fans are immedia-
tely disarmed. If there’s a defrosting cycle in progress, this continues and it finishes to expire of the timeout.
The start on is automatic in condition of alarm disappeared.
Core Probe Alarm
Appears when notified a Core Probe problem. The display visualize the label “Er3.” The buzzer plays. If a time cycle
was in progress is immediately stopped. If a temperature cycle was selected it is not possible to perform it. The start on
appends in condition of alarm disappeared.
Condenser Probe alarm
Notice a problem probe condenser is possible only if turned on. The display visualize the label “Er4.” The buzzer plays.
The alarm doesn’t have effect on the execution of a possible cycle in course but the fans condenser are not connected
to the condenser temperature anymore, they depend of lighting and turning off “off” the condenser conditions. In circum-
stances of alarm, the highest Temperature of Condensation is not managed anymore.
The star on is automatic only in condition of alarm disappeared.
Alarm high Pressure
The display visualize the label “HP.” The buzzer plays.
If there’s a cycle in progress it will be interrupt
The rearmament append in condition of alarm disappeared.
Alarm Low Pressure
The display visualize the label “LP.” The buzzer plays.
If there’s a cycle in progress it will be stopped.
The rearmament append in condition of alarm disappeared.
Alarm overheating of the compressor
The display visualize the label “it Has.” The buzzer plays.
If there’s a cycle in progress it will be stopped.
The rearmament append in condition of alarm disappeared.
Open Door Alarm
The display visualized the label “d-r”.
The buzzer plays
The compressor and the fans condenser are deactivated
The rearmament append in condition of alarm disappeared.
If the label is in STANDBY the opening of the door is signaled only on the displays.
Alarm High Temperature Cold Room
If during a positive (negative) maintenance cycle, the temperature in the cold room is superior to the planned value the
displays DIS1 visualize the label “AH”, the buzzer plays. This alarm doesn’t create any kind of effect.
Alarm Low Temperature Cold Room
IF during a positive (negative) maintenance the temperature in the cold room is inferior to the planned value the displays
DIS1 visualize the label “To the”, the buzzer plays. This alarm doesn’t create any kind of effect.The rearmament is auto-
matic when the temperature in the cold room is superior to the set point.