In circumstances where the supply installation is inadequate for the full charging output of the
charger, refer to the derating guideline and set the maximum output current accordingly when
comissioning a single phase charger.
0 1000 2000 3000 4000
0
2
4
6
8
10
12
0 1 2 3 4 5 6
Test load power, W
Circuit voltage drop at 40A, VAC
Test load voltage drop, VAC
1000W
2000W
3000W
4000W
Calculation of voltage drop at 40A based on test load of known power