14
D. Function
Setting
23
LOOP 1 commands opening and, at end of opening, closes if released (useful if a vehicle
reverses with consecutive loops).If disabled at disengagement of LOOP 1, no closure is
performed.
Y
= closes if LOOP1 is free
no
= disables
24
NOT USED /
25
A.D.M.A.P function
If you enable this function, the safety devices operate according to French standards.
Y
= enables
no
= disables
26
If you enable this function, during closure, the CLOSING SAFETY DEVICES stop movement
and, when disengaged, reverse movement, otherwise they reverse immediately.
Y
=
stops movement
and reverses when
disengaged
.
no
= reverses immediately.
27
NO EFFECT /
A1
PRELAMPEGGIO:
Used for adjusting - in 1 sec steps - the duration of required pre-flashing, from a minimum
of
0
to a maximum of
10
seconds
05
A2
TIMEOUT FOR REVERSING AT CLOSURE:
If you enable this function, during closing, you can decide whether to reverse or stop the
movement when time out elapses (closing stroke limit not reached).
Y
= reversal
no
= block
A3
OPENING AT POWER UP:
In case of a power cut, when power is restored, an opening operation can be commanded
by enabling this function (only if the automated system is not closed, FCC free).
Y
= opening
no
= stays idle
A4
TIME FOR ENABLING FAAC CITY PRESSURE SWITCH:
This is the time after which the unit considers the signal originating from the pressure switch
as the CLOSING TRAVEL-LIMIT.
Can be adjusted from
0
to
59
sec. in 1 second steps. Subsequently, the display changes
to show minutes and tenths of a second (separated by a dot), up to a maximum value
of
4,1
minutes.
4.0
A5
DISABLING OF FAAC CITY PRESSURE SWITCH AT START OF MOVEMENT:
It is possible to disable the travel limit input command at the start of the closing manoeuvre
for a time of 0.4 secs (useful to inhibit the FAAC CITY pressure switch for thrust at rise)
Y
= pressure switch
deactivated on initial thrust
no
=pressure switch always
active
A6
FAAC CITY SOLENOID VALVE POWER SUPPLY CHECK (terminals 22-23):
FAAC CITY K: solenoid valve output usually not supplied with power – supplied with
power during downstroke.
FAAC CITY standard: solenoid valve output usually supplied with power – not supplied
with power during downstroke.
Y
= for FAAC CITY K
no
= for FAAC CITY
standard
A7
POLARITY OF OPENING TRAVEL-LIMIT STOP:
Configuration of the travel-limit stop contact
Y
= NO polarity
no
= NC polarity
A8
POLARITY OF CLOSING TRAVEL-LIMIT STOP:
Configuration of the travel-limit stop contact
Y
= NO polarity
no
= NC polarity
A9
FAAC CITY PRESSURE SWITCH ENABLE (J5):
Detection of the PRESSURE SWITCH contact as safety device during the first upstroke phase
and as limit switch after activation time of FAAC CITY pressure switch (parameter
A4
):
Y
= Operation for FAAC CITY
no
= Standard limit switch
operation
b0
SAFETY ONLY PRESSURE SWITCH FOR FAAC CITY (terminals 7-GND):
Recognition of PHOTOCELL contact as a safety PRESSURE SWITCH but not as travel limit for
FAAC CITY:
Y
=Pressure switch operation
as safety device only
no
= Standard photocell
operation
b1
HOLD CLOSE / HOLD OPEN FUNCTION DELAY:
Delay of the activation of the HOLD CLOSE / HOLD OPEN function (see parameters b3 and
b4). The count starts when the involved limit switch has been reached.
If, at the end of the set time, the limit switch is involuntarily disengaged, the HOLD CLOSE /
HOLD OPEN function is activated.
00
= HOLD CLOSE / HOLD OPEN function activated immediately
01
to
99
= minutes of count before activation of HOLD CLOSE / HOLD OPEN
30
b2
DO NOT MODIFY
30
b3
HOLD OPEN FUNCTION:
If the opening limit switch is involuntarily disengaged, the board commands
automatically a movement for 2 sec. to restore the position; if the opening
limit switch is not engaged during this period of time, the automated system
is activated max. for the operating time “t” see 2nd PROGRAMMING LEVEL:
(parameter
A3
recommended on
Y
if parameter
b3
set on
Y
)
Y
= enables
no
= disables
b4
HOLD CLOSE FUNCTION:
If the closing limit switch is involuntarily disengaged, the board commands automatically a
movement for 2 sec. to restore the position; if the closing limit switch is not engaged during
this period of time, the automated system is activated max. for the operating time “t” see
2nd PROGRAMMING LEVEL:
Y
= enables
no
= disables
St
AUTOMATED SYSTEM STATUS:
Exit programming, memory storage of data and return to gate status display (see
par. 5.1.).