7
if you press F again (and hold it down), the display shows
the name of the next function, etc.
when you reach the last function, press the push-button
F to exit programming, and the display resumes showing
the inputs status.
1ST LEVEL PROGRAMMING
Display Function Default
dF
LOADING PARAMETERS:
00
Neutral condition
0 1
Default FAAC 1 loaded
02
Default RESERVED FOR FAAC
03
Default FAAC CITY loaded
04
Default FAAC CITY K loaded
LEAVE AT
00
IF YOU DO NOT WISH TO MAKE ANY
CHANGE TO THE PROGRAMMING.
For an explanation of the dF parameter
refer to page 8 chapter 5.2.
00
bu
BUS ACCESSORY MENU
For an explanation of this parameter refer to
page 8 chapter 5.3.
LO
FUNCTION LOGICS:
A
Automatic
A1 Automatic 1
E Semiautomatic
P Parking
PA Parking automatic
Cn Condo
CA Condo automatic
rb Faac-City ( traffic bollard logic )
C Dead-man
r Remote
Cu Custom
E
PA
PAUSE TIME:
This operates only if an automatic
logic was selected. Can be adjusted
from
0 to 59 sec. in 1 second steps.
Subsequently, the display changes to
show minutes and tenths of a second
(separated by a dot) and time is adjusted
in 10 second steps, up to the maximum
value of
4.1 minutes.
e.g. if the display shows
2.5, the pause
time will be 2 min and 50 sec
.
20
FO
POWER:
Adjusts motor power.
01 = minimum power
50
= maximum power
50
L1
LOOP 1:
If this function is enabled, the loop
connected to the Loop1 input will have
the OPEN function.
Y = loop1 active
no = loop1 not active
Attention: if the function is not enabled,
loop1 status will nevertheless be available
on one of the outputs, if appropriately set
(see second level programming).
no
Display Function Default
L2
LOOP 2
:
If this function is enabled, the loop
connected to Loop2 input will have the
SAFETY/CLOSE function, i.e. it will operate
as SAFETY during the closing stage, and
will command CLOSE to the board at
release.
Y =
loop2 active
no
= loop2 not active
Attention: if the function is not enabled,
loop2 status will nevertheless be available
on one of the outputs, if appropriately
set.
no
S1
SENSITIVITY LOOP 1
Regulates the sensitivity of the loop:
01 = minimum
10
= maximum
05
S2
SENSITIVITY LOOP 2
Regulates the sensitivity of the loop:
01 = minimum
10
= maximum
05
St
AUTOMATED SYSTEM STATUS
:
Exit programming,
memory storage of data set and return to
automated system status view
.
00
Closed
01
Opening pre-flashing
02
Opening
03
Open
04
In pause
05
Closing pre-flashing
06
Closing
07
Stopped ready to close
08
Stopped ready to open
09
Emergency opening
10
Closing safety device in operation
The display of the automated system
status
St
is of fundamental importance
for the operator assigned to installation/
maintenance, to distinguish the logical
processes the board performs during
movements.
If, for example, the automated system is
in CLOSED state
00
must be shown on the
display. On reaching the command OPEN,
the display will change to
01
, if pre-flashing
is enabled, or directly to
02
(the OPENING
movement), to then display
03
on reaching
the OPEN position.
ENGLISH