B614 32 732998 - Rev.A
Translation of the original instructions
ENGLISH
6. ELECTRONIC INSTALLATION
RISKS
PERSONAL PROTECTIVE EQUIPMENT
F
ALWAYS DISCONNECT THE POWER SUPPLY before
working on the board. Turn power on only after
having made all the electrical connections and carried
out the preliminary start-up checks.
The board cover must never be removed unless the
board is to be replaced. No installation operation
requires the removal of the cover.
6.1 BOARD E614
7 E614 board technical data
230V~ 115V~
Power supply voltage 220-240 V~ 50/60 Hz 115V~ +/-10% 50/60 Hz
Max power 150 W 150 W
Accessories output voltage 24 V
"
24 V
"
Max. accessories load 500 mA 500 mA
Max. BUS 2easy accessories load 500 mA 500 mA
Max. flashing light load 24 V
"
15 W 24 V
"
15 W
Ambient operating temperature -20 °C to +55 °C -20 °C to +55 °C
COMPONENTS
See figure 35
BOARD:
J1 Mains power supply terminal board
J3 BUS 2easy terminal board
J6 Accessory/input terminal board
J7 Connector for XF radio module
J8 Connector for XBAT 24 battery
J10 Terminal board for external detector LOOP1
J11 Connector for encoder
J13 Terminal board for external detector LOOP2
J16 Terminal board for external flashing light
J18 Terminal board for the beam lights
J20 Terminal board for outputs
J21 Connector for integrated flasher
J23 Connector for motor
F3 Board protection fuse (F3 = T2.5A)
DISPLAY Programming display
BOARD:
DL1 Device signalling LED to BUS 2easy ACTIVE
DL2 BUS 2easy “BUS MON“ diagnostic signalling LED
DL3 “RADIO1” (OMNIDEC) signalling LED
DL4 “RADIO2” (OMNIDEC) signalling LED
DL5 Error/alarm signalling LED
DL8 EMER status LED
DL9 STOP/FSW-CL status LED
DL10 CLOSE status LED
DL11 OPEN status LED
DL12 LOOP1 status LED
DL13 LOOP2 status LED